48VDC Power System/ Switch Mode Power Supply /Rectifier System (CE, SGS, ISO)
Capacity: 1600~12600W
1. AC Input: 176~300Vac
2. DC output: 42/53.5/58 Vdc
3. Output power: 1600w
4. Output current: 30A, 60A, 90A, 120A, 200A, 210A
5. LCD display
Main Features:
Application
Configuration:
2 rectifiers + 1 controller + 1 dc distirubtion
Standards:
UL60950 /EN60950
EMC EN55022
RoHS
Capacity: 1600~12600W
1. AC Input: 176~300Vac
2. DC output: 42/53.5/58 Vdc
3. Output power: 1600w
4. Output current: 30A, 60A, 90A, 120A, 200A, 210A
5. LCD display
Main Features:
1U rectifier power shelf up to 1600W
- Wide Input Voltage Range 90Vac-300Vac
- Wide Temperature Range -40 to +75C
- High Power Density
- High Efficiency
- High Power Factor, Low THD
- Active Current Share
- Advanced Battery Management, LVD Control
- Alarm and Protection Function
- Intelligent interface RS232/RS485
- Hot Plug-in
- Front/Rear Access installation
Application
- Wireless Networks
- Access and Optical Network Equipment
- Enterprise Networks
Configuration:
2 rectifiers + 1 controller + 1 dc distirubtion
Standards:
UL60950 /EN60950
EMC EN55022
RoHS
1 Input | |
Input Voltage | 176~300Vac full load |
90-176Vac Derating load | |
Frequency | 45 Hz-65 Hz |
Inrush Current (maximum) | 38A |
Power Factor | ≥0.99 |
Efficiency | ≥91% |
2 Output | |
Vo range | 42/53.5/58 (Vdc) |
Vo Regulation | -0.5/+0.5 (%) |
Output Current | 75A |
Current Share | -5/+5 (%) |
3 Environment | |
Operating Temperature | -40 ºC - 75 ºC |
Humidity | 10% - 90% Non Condensing |
Cooling | Forced Air |
4 Configuration | |
Controller | SC Controller |
Rectifier | CR2000-48 |
DC Distribution | 1*75A Load 1*75A Battery 1*LVD control 4*Alarm Relay Output(programmable) |
5 Other information | |
Dimension | 44.3*482.6*250mm(front access) 44.3*482.6*280mm(rear access) |
Standards | Safety UL60950/EN60950 EMI EN55022 Environment RoHs Compliant |
Communication | RS232/RS485 |
Rectifier No | 2 |